Variable Frequency Transformer Comprehensive Characteristic Tester
- Wrindu
- Shanghai, China
- about 10 working days
- 1000 set/month
- RDHG-E
RDHG-E CT and PT Tester is a new generation of innovative CT and PT testing instrument developed on the basis of traditional transformer volt ampere characteristic ratio polarity comprehensive tester based on voltage regulator, voltage booster and current booster.
Description
RDHG-E Variable Frequency Transformer Comprehensive Tester is a new generation of innovative CT and PT testing instrument developed on the basis of traditional transformer volt ampere characteristic ratio polarity comprehensive tester based on voltage regulator, voltage booster and current booster, widely listening to users' opinions, after a lot of market research and in-depth theoretical research. The device adopts high-performance DSP and FPGA, advanced manufacturing technology, which ensures stable and reliable product performance, complete functions, high degree of automation, high test efficiency. It is a professional test instrument for mutual inductors in the power industry.
Product Features
1. Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.
2. Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
3. Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 30kV.
4. The test meets various transformer standards such as IEC60044-1) and IECC60044-6, and automatically selects which standard to test according to the transformer type and level.
5. Friendly and beautiful interface, graphical LCD display
6. The Variable Frequency Transformer Comprehensive Tester can store 1000 groups of test data that won’t be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.
7. Test is simple and convenient, one-click can complete tests of CT secondary resistance, excitation, ratio and polarity.
8. The panel is equipped with a printer, which can print the generated test report.
9. Light weight, easy to carry.
Specifications
Test purpose | CT, PT | |
output | 0 ~ 180Vrms, 12Arms, 36A (peak value) | |
Voltage measurement accuracy | ±0.1% | |
CT transformation ratio measurement | Range | 1~10000 |
accuracy | ±0.2% | |
PT transformation ratio measurement | Range | 1~10000 |
accuracy | ±0.2% | |
phase measurement | accuracy | ±3min |
resolution | 0.3min | |
Secondary winding resistance measurement | Range | 0~300Ω |
accuracy | 1%±1mΩ | |
AC load measurement | Range | 0~300VA |
accuracy | 1%±0.1VA | |
Input power supply voltage | AC220V±10%,50Hz | |
Work Environment | Temperature: - 10 ℃ ~ 50 ℃, humidity: ≤ 90% | |
What Tests Can the RDHG-E Perform on CTs and PTs?
The RDHG-E Variable Frequency Transformer Comprehensive Tester supports several tests for current transformers (CTs) and potential transformers (PTs). It helps engineers check transformer performance during commissioning, maintenance, and troubleshooting.
| Test Function | Purpose |
|---|---|
| Excitation Test | Checks the excitation curve and knee-point characteristics. |
| Ratio Test | Verifies the transformation ratio against the rated value. |
| Polarity Test | Checks the polarity relationship between primary and secondary terminals. |
| Winding Resistance Test | Measures secondary winding resistance to identify possible connection or winding problems. |
| Burden Test | Measures the connected secondary burden. |
| Ratio Error and Phase Displacement | Evaluates transformer measurement performance. |
How Does CT Excitation Testing Help Engineers?
CT excitation testing shows how excitation current changes as the applied voltage increases. The excitation curve helps engineers identify the knee point and assess the magnetic characteristics of the transformer.
The RDHG-E uses a low-frequency test method and supports CT knee-point voltage testing up to 30 kV, according to the product specifications. Its rated output is 0–180 Vrms, 12 Arms, with a peak current of 36 A.
The instrument can also calculate parameters such as the accuracy limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), and remanence coefficient (Kr).
What Should Engineers Check Before CT/PT Testing?
Transformer data: Confirm the rated ratio, accuracy class, and terminal markings.
Test voltage: Select the appropriate test settings for the transformer type and test procedure.
Safety: Isolate the equipment and follow approved safety procedures before connecting test leads. Never leave an energized CT secondary circuit open.
Test requirements: Select the required tests according to the equipment manufacturer's instructions and applicable standards.
How Does the RDHG-E Manage Test Data?
The RDHG-E can store up to 1,000 groups of test records. Users can transfer data to a computer through a USB disk and generate Word reports. A built-in printer also allows reports to be printed directly from the instrument.
These functions help engineers keep test records for maintenance, commissioning, and future comparison.
Wrindu Standards and Technical Support
The original specifications list IEC 60044-1 and IEC 60044-6. As these belong to an older standards series, confirm the applicable standard edition and supported test procedures before ordering.
Wrindu provides a one-year warranty for the RDHG-E CT/PT Comprehensive Tester. The team also offers technical guidance to help customers with equipment operation and testing procedures. For product support or warranty assistance, please contact Wrindu.