SF6 Decomposition Tester

  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
  • SF6 Decomposition Tester
SF6 Decomposition Tester
  • Wrindu
  • Shanghai, China
  • about 25 days
  • 5000 set/month
  • RDFJ-708B

The RDFJ-708B SF6 gas decomposition products tester provides a simple on-site detection method for SF6 decomposition products. During use, The SF6 decomposition component analysis is connected to a gas chamber filled with SF6 gas equipment under pressure, and SF6 gas is allowed to flow through the electrochemical sensor at a certain flow rate. The sensors all use high-quality imported sensors with reliable performance and long-life design, ensuring the accuracy and reproducibility of the measurement results.

RDFJ-708B SF6 Decomposition Products Tester

ppm purity decomposition sf6 gas analyzer

Product features:

1. Long life detection components

2. Direct measurement without colorimetric tube or sensor

3. High accuracy and good repeatability

4. Built-in pressure regulator and electronic mass flow meter

5. Large color LCD display

6. Lithium battery power supply, AC and DC dual-use

7. The Sf6 Comprehensive Analyzer comes with cleaning function

 

Product specifications and technical parameters

Name

Technical parameters

Measuring range

SO2:0 ~ 100μL/L

H2S:0 ~ 100μL/L

 CO: 0 ~ 1000μL/L

HF: 0 ~ 10μL/L

Measuring accuracy

SO2:when the measured value ≤10μL/L, the error±0.2μL/L

when the measured value≥10μL/L, the error≤±3%

H2S:when the measured value≤10μL/L, the error±0.2μL/L

when the measured value≥10μL/L, the error≤±3%

CO:  when the measured value≤50μL/L, the error±0.5μL/L

when the measured value≥50μL/L, the error≤±4%

HF:  the error of measured value≤±0.1μL /L

Repeatablity

SO2:when the measured value≤10μL/L,the repeatablity≤±0.1

when the measured value≥10μL/L,the repeatablity≤±2%

H2S:when the measured value≤10μL/L,the repeatablity≤±0.1

when the measured value≥10μL/L,the repeatablity≤±2%

CO: when the measured value≤50μL/L,the repeatablity±0.3

when the measured value≥50μL/L,the repeatablity≤±3%

HF: the repeatability of measured value≤±0.1

Resolution

0.1μL/L

Sampling flow

0.2L/min

Measuring time

≤180S

Working environment

Temperature-10℃ ~ +50℃,Humidity0 ~ 90%RH

Supply power

Lithium battery power supply, AC and DC dual-use, automatic switching, overcharge and over discharge protection function

Dimension

330(mm)×220(mm)×150(mm);

Weight

4.8KG

 SF6 Decomposition Tester

SF6 gas analysis equipment set


Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right