RDYZ-II Surge Arrester Discharge Counter Tester | Wrindu
- Wrindu
- Shanghai, China
- about 10 working days
- 5000 set/month
- RDYZ-III
RDYZ-II surge arrester testing equipment is a special instrument for detecting the discharge counter at the lower end of arrester in substations, hydro thermal power plants and large self provided power plants. The Discharge Counter Detector can not only check the number of lightning strokes, but also check the leakage current.
Product features
The test principle adopts the capacitor charging and discharging method: the charging time is short and the discharging speed is fast;
Easy operation: one key to complete the automatic charging and discharging process, and the automatic test time interval is adjustable from 3S to 8s;
Wide application range: high voltage output 200V ~ 1600V adjustable, step 200V, can meet the action voltage of various counters;
Safe and reliable: the instrument shell is made of ABS plastic, the high-voltage output is free of metal exposure, and the operator is safe and will not be shocked;
Multiple test times: one charge can be operated continuously for more than 2000 times;
Self-discharge function: after charging, if there is no test, the high voltage will be automatically released within two minutes.
Convenient test: this instrument is equipped with a set of test lines and a pull rod line, which can meet the test needs of different methods during the test.
Product specifications and technical parameters
1. Output voltage: 200 ~ 1600 V adjustable;
The voltage regulation is divided into eight gears from 0 to 7, and the corresponding output voltage values are as follows:
0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
200V | 400V | 600V | 800V | 1000V | 1200V | 1400V | 1600V |
2. Capacitance: 10uF;
3. Discharge current: more than 100A;
4. Power supply mode: rechargeable lithium battery;
5. Dimensions: 238mm×134mm×55mm
What Is a Surge Arrester Discharge Counter Tester Used For?
A surge arrester discharge counter records the number of discharge operations during lightning strikes or power system overvoltage events.
Over time, the counter may experience mechanical wear, electrical faults, or poor contact. A counter that fails to operate correctly may record an inaccurate number of discharge events.
The RDYZ-II helps maintenance personnel check counter operation without relying only on its historical readings.
Its main applications include:
Checking the operating response of lightning arrester discharge counters.
Verifying whether the counter advances after a simulated discharge pulse.
Checking arrester leakage current as supported by the selected test connection.
Performing routine inspection of surge arresters in substations.
Supporting preventive maintenance in power generation facilities.
How Does the RDYZ-II Surge Arrester Tester Work?
The RDYZ-II uses a capacitor charging and discharging principle to generate high-voltage test pulses.
Its internal capacitor charges to the selected voltage and then releases stored energy through the test circuit. The resulting discharge pulse simulates the electrical input required to activate a surge arrester discharge counter.
The output voltage can be adjusted from 200 V to 1600 V in eight steps.
The basic testing process is:
Connect the test leads to the discharge counter according to the instrument instructions.
Select the required output voltage.
Start the automatic charging and discharging process.
Observe whether the counter responds to the test pulse.
Repeat the test when necessary to check consistent operation.
The automatic test interval can be adjusted from 3 to 8 seconds, reducing the need for repeated manual operation.
What Is the Discharge Current of the RDYZ-II?
The RDYZ-II has a rated discharge current specification of more than 100 A. And This high-current pulse is generated through its internal capacitor charging and discharging circuit. So the instrument uses a 10 μF capacitor to store electrical energy before discharge.
The stored energy is determined by the charging voltage:
Where:
E= Stored energy in joules.
C = Capacitance in farads.
V = Charging voltage in volts.
For a 10 μF capacitor, the theoretical stored energy at 1600 V is 12.8 J.
This value describes the capacitor's stored energy, not the energy necessarily delivered to the discharge counter during each test.
Why Choose Wrindu Surge Arrester Testing Equipment?
Wrindu is a China OEM manufacturer of high-voltage electrical testing equipment and power testing solutions.
Established in 2014, Wrindu provides equipment design, R&D, manufacturing, and OEM/ODM services. The company operates a manufacturing facility covering more than 50,000 m², with 6 production lines and over 200 employees.
Wrindu supplies testing equipment for power utilities, substations, transformer manufacturers, and electrical maintenance companies.
The RDYZ-II is designed to support routine surge arrester discharge counter inspections with adjustable output voltage and automatic pulse generation.
Customers can contact Wrindu for product specifications, technical information, and OEM/ODM requirements.